Letter from the Editor: Welcome to the November 2009 issue of Fire Protection Engineering Emerging Trends, Fire Protection Engineering magazine's 8-time-per-year e-newsletter that deploys on the off-months of the magazine. Each issue will highlight a new trend and/or innovation in the fire protection engineering industry. This issue will focus on specific requirements for fire pumps in high-rise buildings in the 2010 edition of NFPA 20.
Please enjoy the November issue and thank you for your continued support!
Sincerely,

Morgan J. Hurley, P.E., FSFPE
Emerging Trends in Fire Pumps
By Gayle Pennel
With the advent of taller high rise buildings, and concern that some of the current design practices do not provide the high level of reliability needed, NFPA 201 developed specific requirements for fire pumps installed in high rise buildings in the 2010 edition.
High rise buildings that are beyond the pumping capacity of the fire department must be self-contained and the occupants may need to be protected in place. This makes the reliability of fire protection systems critical.
ADVERTISEMENT:
EST3-Sixty: UL listed Fire Alarm and Mass Notification
EST3-Sixty™ paints a panoramic picture of an unfolding situation with fully-integrated field-proven crisis management technology. It is a top-level, facility-wide solution that handles multiple threats by leveraging the power behind EST3 Emergency Communications. EST3-Sixty provides the right information at the right time to the people who need to know. It offers response personnel the tools they need, not only to warn people of imminent danger, but to guide them to safety as well. And it offers building owners the security of a fully UL Listed solution – an edge that ensures outstanding performance and ongoing compliance for years to come. To learn more, go to http://gesecurity.com/mnec.
In general, the new fire pump requirements in the 2010 edition of NFPA 20 are intended to maintain the availability of the required fire protection water flow even with a single failure of any component for buildings where there are stories that are beyond the pumping capacity of the fire department. These requirements include:
- Auxiliary power for electric motor driven fire pumps is required whenever the fire pump serves any floors that are beyond the pumping capacity of the fire department.
- Access to fire pump rooms is required directly through an exterior door or through a two hour rated enclosed passageway connected to an exterior door or an enclosed stairway.
- Water tank(s) supplying fire pump(s) that serve floors beyond the pumping capacity of the fire department:
- Must hold the full fire protection water demand.
- Must be subdivided and piped so that a minimum of 50% of the total fire protection water demand is available with any one compartment or tank out of service.
- Must have a minimum of two automatic fill valves. Each fill valve, when operating independently, is required to refill the system at a rate equal to or greater than the fire protection demand rate.
- The water supply/fire pump arrangement must be such that the full fire protection water demand can be met even with the failure of any single component. This requirement can be met with a properly arranged backup fire pump, or possibly from a tank located higher in the building.
ADVERTISEMENT:
SFPE Job Board
http://jobs.sfpe.org/
The Society of Fire Protection Engineers and Fire Protection Engineering magazine are pleased to offer an Internet Job Board site featuring career opportunities in fire protection engineering.
http://jobs.sfpe.org/ is designed for communicating the availability of employment opportunities in the fire protection engineering market. This special job board is ideal both for those seeking to fill positions and those looking for employment opportunities in fire protection engineering.
Job categories include: • Consulting • Research & Testing • Government • Fire Equipment Manufacturing & Installation • Insurance • Education
Whether you're looking to make a career move, or you need to fill a fire protection engineer opening, http://jobs.sfpe.org/ is just a click away!
A requirement that fire pumps operating in series must be located in the same room was included by the committee responsible for developing NFPA 20, but was later removed by a floor vote at the NFPA Annual Meeting. This requirement is likely to be revisited and included in future editions of NFPA 20.
In the current edition of NFPA 14,2 a change was enacted which allows "master" pressure control valves to supply whole standpipe or sprinkler system zones. Currently, NFPA 14 has a pressure limit of 350 psi (2.4 MPa), which limits the applicability of the "master" pressure control valves. There is a proposal to remove the pressure limit for express risers in the next edition of NFPA 14. Currently, fire pumps that develop approximately 250 psi (1.7 MPa) of net pressure are available. If the proposal passes, this will likely lead to pump manufacturers listing fire pumps rated for higher pressures, so that a single fire pump rated for 500 psi (3.4 MPa) or more could be used to supply multiple standpipe or sprinkler zones.
|
ADVERTISEMENT:
Careers in Fire Protection Engineering
Interested in a career in fire protection engineering? Know someone who is? Pondering a new career? Visit FPEmag.com/Careers to access an exciting career guide with valuable information on the field of fire protection engineering. |
 |
NFPA 20 was also modified to allow variable speed drivers to maintain a pump suction pressure as well as the pump discharge pressure.
Limited service controllers have been a subject of debate for many years. These controllers are limited to 30 horsepower (22 kW), and were originally intended to lower the cost of retrofitting schools. Over the years, additional requirements added to address safety and other concerns have narrowed the distinction and cost differential between limited service and full service controllers. Over the past few code cycles, a proposal to eliminate limited service controllers from NFPA 20 has been rejected by the NFPA 20 committee by a narrower margin each cycle, until it finally passed in the current (2010) cycle. However, limited service controllers were restored the 2010 edition by floor action at the NFPA Annual Meeting. This issue will most likely be considered again in the 2013 NFPA 20 cycle.
Gayle Pennel is with Schirmer Engineering Corporation
1 NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, National Fire Protection Association, Quincy, MA, 2010. 2 NFPA 14, Standard for the Installation of Standpipe and Hose Systems, National Fire Protection Association, Quincy, MA, 2007.
Related Articles: FPE Winter 2009 – Supplying Water for High-Rise Construction Projects Large construction projects can take many years to complete from start to finish. This is especially true when the final building height will be over 400 feet (120 meters). As a building increases in height, it becomes necessary to provide fire protection in the upper floors. Typically, the building's automatic sprinkler system cannot be made fully operational until the building nears completion. Therefore, the primary means of providing fire protection in the upper floors of a building under construction is through the use of a standpipe system. The most desirable means of providing protection to a high-rise construction project will depend on the nature and duration of the project. It will also vary with the capabilities of the local fire department. In all such cases, operating procedures of the fire department must be integrated into the system operation. READ MORE
FPE Winter 2009 – Fire Sprinkler Systems During Construction When should a fire sprinkler system be brought online? READ MORE
FPE Summer 2006 – High-Rise Buildings: What Should We Do About Them? The World Trade Center events of September 11, 2001, focused the world's attention on high-rise buildings. Since that time, there have been several other events that have kept the world's attention on high-rise building fire safety, including fires in Madrid, Venezuela, and two in Chicago. Major code groups in the United States and around the world have begun to seriously look at high-rise building safety and to question whether enough is being done. The United States Government is conducting a major study, through the National Institute of Standards and Technology (NIST), to evaluate high-rise building safety. This article looks at some of the events that have occurred, evaluates lessons learned, discusses some of the recommendations currently being considered in high-rise safety design, and suggests ways forward to look at fire safety design and high-rise structures. READ MORE
ADVERTISEMENT:
Join the Society of Fire Protection Engineers
The Society of Fire Protection Engineers (SFPE) is the professional organization that represents fire protection engineers worldwide. Through its membership of over 4,500 professionals and 59 chapters, SFPE advances the science and practice of fire protection engineering internationally. For more information, visit http://www.sfpe.org/Membership.aspx.
For questions concerning delivery of this e-Newsletter, please contact our Customer Service Department at (216) 931-9733 or FPEmag.com.
Copyright 2009, Penton Media, Inc. All rights reserved. This eNewsletter is protected by United States copyright and other intellectual property laws and may not be reproduced, rewritten, distributed, re-disseminated, transmitted, displayed, published or broadcast, directly or indirectly, in any medium without the prior written permission of SFPE and Penton Media, Inc.
|