Letter from the Editor: Welcome to the May 2009 issue of Fire Protection Engineering Emerging Trends, Fire Protection Engineering magazine's 8-time-per-year e-newsletter that deploys on the off-months of the magazine. Each issue will highlight a new trend and/or innovation in the fire protection engineering industry. This issue will focus on issues identified within the International Code Council's ad hoc committee on terrorism-resistant buildings that may impact fire protection engineering.

Please enjoy the May issue and thank you for your continued support!

Sincerely,

Morgan J. Hurley, P.E.


Issues Identified Within ICC'S Ad Hoc Committee on Terrorism-Resistant Buildings That May Impact Fire Protection Engineering

By John R. Battles, P.E.

The International Code Council (ICC) Board of Directors authorized the creation of the Ad Hoc Committee on Terrorism-Resistant Buildings in mid-2004. The Ad Hoc Committee process has been used frequently by the ICC to enable the devotion of sufficient time and resources to a particular topic or subject area. A call for committee members was posted in July, 2004, and the Ad Hoc Committee convened for the first time in February of 2005 by conference call.

About six months into the Committee's efforts, the NIST World Trade Center (WTC) Study1 was released to the public (in September, 2005).

The Committee reviewed the report and developed a list of action items within the purview of the model codes based upon the recommendations contained within the report. The items addressed include the following issues: progressive collapse (NIST Recommendation #1), building burnout (NIST Recommendation #4 & #8), spray-on fire resistant materials (NIST Recommendation #6), redundancy of active fire protection systems (NIST Recommendation #12), stairway width (NIST Recommendation #17 & #18), stairway remoteness (NIST Recommendation #17 & #18), stairway shaft robustness (NIST Recommendation #17 & #18), and command and control systems (NIST Recommendation #24).


Article continues below

ADVERTISEMENT:

Bosch's FPA-1000-UL analog addressable control panel sets new standards for price and performance.

  • Alarms for carbon monoxide and other gases
  • IP remote programming and access via an on-board web server
www.boschsecurity.us


A total of fourteen code changes were submitted during the 2006/2007 code cycle. Ten unsuccessful code change proposals were amended in accordance with public comments and re-submitted for the 2007/2008 code cycle.

The following are the changes implemented by the Ad Hoc Committee on Terrorism-Resistant Buildings consistent with the NIST WTC Recommendations impacting fire protection engineering that will appear in the 2009 International Building Code:

  • Increases the reliability of automatic sprinkler systems in buildings more than 420 feet (128 meters) in height.
    Each sprinkler zone must be supplied by a minimum of two risers. Each riser must be placed in remotely located stairs and supply sprinklers on alternate floors.
  • Increases the cohesive/adhesive bond strength of cured, sprayed fire-resistive materials (SFRM) for high rise buildings.
    The minimum bond strength for all buildings regardless of the height of buildings was 150 pounds per square foot (psf) (7200 Pa). The bond strength has increased by nearly 3 times to 430 psf (21,000 Pa) where the height of buildings is more than 75 feet (23 meters) and up to 420 feet (128 meters). The bond strength has increased by nearly 7 times to 1,000 psf (48,000 Pa) where the building height is more than 420 feet (128 meters).


ADVERTISEMENT:

SFPE Job Board

http://jobs.sfpe.org/

The Society of Fire Protection Engineers and Fire Protection Engineering magazine are pleased to offer an Internet Job Board site featuring career opportunities in fire protection engineering.

http://jobs.sfpe.org/ is designed for communicating the availability of employment opportunities in the fire protection engineering market. This special job board is ideal both for those seeking to fill positions and those looking for employment opportunities in
fire protection engineering.

Job categories include:
• Consulting
• Research & Testing
• Government
• Fire Equipment Manufacturing & Installation
• Insurance
• Education

Whether you're looking to make a career move, or you need to fill a fire protection engineer opening, http://jobs.sfpe.org/ is just a click away!


  • Adds application requirements for sprayed fire-resistive materials (SFRM).
    The application must be in accordance with the manufacturer's installation instructions including, but not limited to, substrate temperature and surface conditions, and SFRM handling, storage, mixing, conveyance, method of application, curing and ventilation. The substrate to receive SFRM is required to be clean and free of any condition that prevents adhesion. For SFRM that is to be applied over primers, paints, or encapsulants other than those specified in the listing, the material must be field tested in accordance with ASTM E736.2 The finished condition of the installed SFRM, upon complete drying or curing, shall not exhibit cracks, voids, spalls, delamination or any exposure of the substrate.
  • Enhances special inspection requirements for sprayed fire-resistive materials.
    Special field inspection of SFRM is required to be performed after the rough installation of electrical, mechanical and plumbing systems. Physical and visual tests must be performed regarding the condition of substrates, thickness of application, density, bond strength – adhesion/cohesion, condition of finished application, and field bond tests needed to qualify application over certain primers, paints, and encapsulants.
John Battles, P.E., is with the International Code Council

  1. Final Report of the National Construction Safety Team on the Collapses of the World Trade Center Towers. NIST NCSTAR 1. National Institute of Standards and Technology, 2005.
  2. ASTM E736 "Standard Test Method for Cohesion/Adhesion of Sprayed Fire-Resistive Materials Applied to Structural Members." ASTM International, West Conshohocken, PA, 2006.


ADVERTISEMENT:

Careers in Fire Protection Engineering

Interested in a career in fire protection engineering? Know someone who is? Pondering a new career? Visit FPEmag.com/Careers to access an exciting career guide with valuable information on the field of fire protection engineering.


ADVERTISEMENT:

Join the Society of Fire Protection Engineers

The Society of Fire Protection Engineers (SFPE) is the professional organization that represents fire protection engineers worldwide. Through its membership of over 4,500 professionals and 59 chapters, SFPE advances the science and practice of fire protection engineering internationally. For more information, visit http://www.sfpe.org/Membership.aspx


Related Articles:
FPE Fall 2008 - Impact of Fires on the Built Environment Over the Past 10 Years
During the last 10 years, the reduction in annual home fire deaths has slowed, and the impact of uncontrolled fire on the built environment has focused attention on solutions to the fire challenge. A select group of fires affected the built environment by shaping code writing and code enforcement. Fires in assembly spaces, high-rise office buildings, nursing homes and atrium buildings impacted the fire services, authorities having jurisdiction, code-writing organizations and the general public.
READ MORE

FPE Fall 2006 – SFRM Commissioning and Field Testing
Sprayed Fire-Resistive Material (SFRM), more commonly referred to as spray-applied fireproofing, is a passive fire protection material intended for direct application to structural building members. The intent of this material is to increase the fire resistance characteristics of those members, primarily through insulation. The fire resistance of structural building elements provides an important contribution to the fire protection system design implemented in building construction. Commissioning and field testing of SFRM is not only important in new construction, but now with the recent enactment of renovation requirements in many jurisdictions, such as Local Law 26 of 2004 in New York City, retroactive special inspection of SFRM in existing structures is becoming a requirement whenever SFRM is exposed as part of a building renovation.
READ MORE

FPE Spring 2003 - Study of Building Performance in the WTC Disaster
The impacts of aircraft into the twin towers of the World Trade Center set off a chain of events seen via television coverage by many of the world's population on September 11, 2001. These aircraft damaged portions of the structure of the twin towers and also initiated fires on several floors. By the end of the day, four buildings collapsed, three buildings were severely damaged by fire, and seven buildings sustained significant damage, while numerous others suffered minor damage. In late September, the Building Performance Study (BPS) team was formed to study the response of the affected buildings to impacts and fires.
READ MORE



For questions concerning delivery of this e-Newsletter, please contact our Customer Service Department at (216) 931-9733 or FPEmag.com.

Copyright 2009, Penton Media, Inc. All rights reserved. This eNewsletter is protected by United States copyright and other intellectual property laws and may not be reproduced, rewritten, distributed, re-disseminated, transmitted, displayed, published or broadcast, directly or indirectly, in any medium without the prior written permission of SFPE and Penton Media, Inc.

[Get Copyright Permissions] E-MAIL | PRINT | SAVE | REPRINTS
:: Issue 27 ::
About | Site Map | Privacy Statement | Terms of Use
Copyright © 2010 Penton Media, Inc.